Improved working environment in Ahus Sterile Unit

Imagine working in an environment where the constant clatter of metal trolleys, the hum of industrial washing machines, and sound reflections from hard surfaces create an unrelenting cacophony. This was the daily reality for the dedicated staff at the sterile unit of Akershus University Hospital (Ahus), one of Norway’s largest hospitals, located just outside Oslo.

The sterile unit

At the sterile unit in Ahus, every piece of surgical equipment is meticulously cleaned, packed, and prepared for the next procedure. The staff’s ability to concentrate and communicate effectively is vital – not only for their own wellbeing but also for the safety of the patients who depend on their precision and care.

Although Ahus is a relatively modern hospital, having opened in 2006, the acoustics in the sterile unit left much to be desired. The unit is divided into clean and unclean zones. In the unclean zone, used surgical equipment is received and initially cleaned. It then passes through washing machines before being transferred to the clean side, where it is prepared for reuse. The combination of hard surfaces – gypsum, concrete, and linoleum – and the noise from machines and trolleys created a demanding work environment. High noise levels drained staff energy, making it difficult to focus and communicate effectively.

A modern, clean laboratory with stainless steel workstations, computers, and scientific equipment. Large glass windows separate the lab from another room with industrial machines and conveyor belts. Bright overhead lighting.

The combination of hard surfaces and the noise from machines and trolleys in the sterile unit created a demanding work environment.

A modern, sterile hospital sterilisation room with metal racks holding surgical instruments. A person in green scrubs walks through the bright, clean space. Monitors and cupboards line the white walls.

The staff’s ability to concentrate and communicate effectively is vital – not only for their own wellbeing but also for the safety of the patients who depend on their precision and care.

Challenges in a demanding environment

Operating around the clock, the sterile unit at Ahus handles a consistently high workload. The staff play a critical role in ensuring that all surgical equipment is ready for use. However, the persistent noise from machinery and the metallic clatter of trolleys made it difficult to concentrate and perform tasks efficiently. Communication was also hindered, often requiring staff to raise their voices to be heard, which led to frequent misunderstandings.

Measures to improve the working environment

Recognising the need for improvement, a project was launched to address the acoustic challenges in the sterile unit. In the initial phase, sound measurements and staff surveys were conducted to assess the physical working environment. To meet strict hygiene and cleaning requirements, a new type of acoustic ceiling – Ecophon Hygiene Performance™ B – was selected. These panels are installed directly onto the existing slab and are designed to withstand thorough washing and disinfection, making them ideal for sterile environments.

A modern, clean laboratory with empty stainless steel racks, large windows, computer monitors, and various equipment. The space appears organised and brightly lit, suggesting a sterile work environment.

To meet strict hygiene and cleaning requirements, a new type of acoustic ceiling – Ecophon Hygiene Performance™ B – was selected.

A modern, sterile laboratory with bright overhead lighting, white walls, digital displays, and stainless steel equipment. The room appears organised with clean workstations and large windows.

The acoustic panels are installed directly onto the existing slab and are designed to withstand thorough washing and disinfection, making them ideal for sterile environments.

Results before and after implementation

Prior to the acoustic improvements, staff reported significant noise from machines, trolleys, and containers, which negatively impacted their ability to concentrate and perform tasks effectively. Many described the physical working environment as challenging, particularly due to the noise.

Following the installation of the acoustic panels, most respondents reported a noticeable improvement in the working environment, with reduced noise levels and better conditions for concentration and communication.

Key findings:

  • Average sound pressure level reduced by 5 dB
  • Reverberation time reduced from 1.04 seconds to 0.43 seconds
  • Sound peaks reduced by 5 dB

Sound pressure levels (SPL) were measured both near the washing machines and at the far end of the room, before and after treatment:

  • Before treatment: the difference between zones was 1.7 dB
  • After treatment: the difference increased to 5.3 dB

This indicates that the acoustic treatment significantly reduced sound propagation across the room. In other words, noise from the machines no longer travels as far, meaning staff working farther away are now less exposed to it.

Bar chart comparing noise levels before and after acoustic treatment: LAeq reduced from 67.3 dB to 62.4 dB, LAFmax reduced from 94.9 dB to 89.8 dB. Grey bars show before, yellow bars show after.

Following the installation of acoustic panels, the average sound pressure level was reduced by 5 dB (LAeq: the average sound energy, LAFmax: the maximum A-weighted sound level).

Table comparing reverberation times before and after acoustic treatment across frequencies from 125 Hz to 8 kHz, showing a T20 A mean reduced from 1.04 to 0.43 after treatment.

The reverberation time reduced from 1.04 seconds to 0.43 seconds.

Collaboration and communication

Before the acoustic improvements, noise from machines and metallic sounds severely impacted concentration and efficiency. After the measures were implemented, many staff members noticed a marked improvement – particularly in the packing room – although some noise issues remained.

The improvements also had a positive effect on collaboration and communication. Previously, noise led to frequent misunderstandings and made it difficult to hear one another without shouting. After the changes, staff reported fewer misunderstandings and found it easier to communicate at normal speaking volumes.

Moreover, the changes had a significant impact on staff wellbeing. Before the improvements, many felt exhausted after their shifts and lacked energy for leisure activities. Post-implementation, they reported feeling less fatigued and more energised in their personal lives.

Conclusion

The acoustic measures implemented at the sterile unit at Ahus have had a profoundly positive impact on the working environment. Reduced noise levels have improved both concentration and communication, contributing to a more efficient and pleasant workplace. While there is still room for further enhancements – such as additional noise reduction and improved lighting – the results so far clearly demonstrate that these measures have significantly enhanced staff wellbeing and productivity.